6�- TECHNICAL FEATURES
Power Supply
Voltage 110V AC o 230V AC
Tolerance -20%, +20%
Frequency 50 Hz - 60 Hz
Maximun consumption 6 VA ( 110V AC) - 6 VA ( 230V AC)
Voltage pulse 4KV
Installation category CAT III 300V
Current measurement circuit
Sensor input Transformer type TP-WG, WG o WGC to 500/1
Measurement system short circuit
Frequency 50Hz -60Hz
Accuracy in measurement
Accuracy current measurement < 10%
Characteristics of trip relay TRIP
Maximum voltage open contacts 1000V AC
Isolation voltage 2500V AC
Thermal current, Ith 10A
Maximum switching power 2500 VA
Electrical life ( 3A) 30*10
3
Characteristics of auxiliar relay AUX
Maximum voltage open contacts 1000V AC
Isolation voltage 2000V AC
Thermal current, Ith 5A
Maximum switching power 1250 VA, 150W
Electrical life ( 3A) 10
5
Environmental characteristics
Work temperature -10ºC ... +50ºC
Storage temperature -25ºC ... 70ºC
Humidity (without condensation) 5 ... 95%
Maximum altitude 2000 m
Pollution resistance Category 2
Protection degree IP40
Mechanical caracteristics
Dimensions 35x112x84 mm
Weight 150gr
Housing Polycarbonate V0
Standards
Low-voltage switchgear and controlgear � Part 2:
Circuit-breakers
IEC 60947-2 Anexo M: 2011
Electrical accessories - Residual current monitors for
household and similar uses (RCMs)
IEC 62020: 1998
23
Instruction Manual
RGU-2 Earth Leakage Relay