Circutor RGU2 Series Instrukcja Użytkownika Strona 16

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 28
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 15
PROG
Trip delay time, td
The current value will start ashing. Press the RESET key gradually to
browse all programming values (Tabla 3).
Accept with the PROG key.
PROG
Trip current, td
The current value will start ashing. Press the RESET key gradually to
browse all programming values (Tabla 3).
Accept with the PROG key.
If changes have been applied, SAVE will be displayed for 3 sec-
onds and the unit will exit the programming screens.
If changes have not been applied, EXIT will be displayed for 3 sec-
onds and the unit will exit the programming screens.
PROG
Note: If you reach the last value of the Trip current to be congured and you do not press the
PROG key to accept the changes, the unit will exit the programming screen after 5 seconds
and the changes will not be saved.
Table 3:Relationship of Currents and Trip Times to be programmed�
Trip current IΔn Trip time td
30mA IN ( Instantaneous )
(1)
0.1A SE (Selective)
(1)
0.3A 0.1s
0.5A 0.2s
1A 0.3s
2A 0.5s
3A 0.8s
5A 1s
2s
3s
5s
(1)
The trip curves are shown in Appendix A
5.6.- PROGRAMMING
5�6�1 TRIP CURRENT IΔn and TRIP DELAY TIME td
The earth leakage protection screen must be displayed to program the current and delay time