9.4.- CirLAMP Node DALI
AC power supply
Mode Self-powered
Rated voltage 184 ... 276 V ~
Frequency 50/60Hz
Consumption 2W 16VA
Installation category CAT III 300 V
Voltage measurement circuit
Voltage measurement margin 184 ...276 V ~
Input impedance 600 M
Installation category CAT III 300 V
Current measurement circuit
Current measurement margin 0.1 ... 3 A
Minimum measurement current (Istart) 0.08 A
Installation category CAT III 300 V
Measurement accuracy
Voltage measurement < 5% of full-scale
Current measurement < 5% of full-scale
Active and reactive power measurement < 5% of full-scale
Relay output: Control relay ON/OFF
Maximum voltage, open contacts 250 V ~
Maximum current 10 A
Maximum switching power 2500 W (AC1)
Electrical life (at full load) 100x10
3
cycles
Mechanical life 10x10
6
cycles
Communications Protocol DALI
Output voltage 15 V
Current 12 mA
Peripheral admitted No� 1
Standard EN-62386-101:2009, EN-62386-102:2009
PLC (Power Line Communications)
Hardware CENELEC B DCSK
Baud rate 2400 bauds with repeater management
Protocol CirPLC (DCSK)
Insulation
Alternating voltage 4 kV RMS 50 Hz for 1 minute
Overimpulse
1.2/50 μs 0R source impedance 2 kV UNE-EN 61000-4-5:2007 + CORR:2010