Circutor computer SMART III-Fast Series Instrukcja Użytkownika Strona 98

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 108
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 97
The keydecreasesthedigitvalue�
The keyskipstothepreviousdigit�
The keyskipstothenextdigit�
Press tovalidatethedata;the symboldisappearsfromthedisplay
Lo Valueand HI Value:
Maximum value: 9999�
Minimum value: 1
Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,5�27�-
SIMULATION SCREEN
5�24�-TEMPERATUREALARM
Inthispointthethresholdsabovewhichthe
temperaturealarm(E10)isactivatedcanbe
configured�
Thealarmmustbeenabled(5�19�- ENABLING
ALARMS”
Pressthe keytoentereditingmode�Itis
identifiedbythe symbolandtheblinkingof
thedigitstobemodified�
Theparameterstobeconfiguredare:
TheLo value : whentheunitexceedsthisvaluefor30minutes,alarmE09 is
triggered,andifalarmE11 is enabled, the SMART III FASTunitentersNo Connection
statusandactivates alarmE11
TheHI value: iftheunitexceedsthisvaluefor30seconds,alarmE09istriggered,
andifalarmE12isenabled,theSMART III FASTunitentersDisconnection statusand
activates alarmE12
IftheunitfallsbackundertheLo valuefor10minutes,itdeactivatesthealarmsandreturns
tothenormaloperatingstatus�
98
Computer SMART III FAST
Instruction Manual
Przeglądanie stron 97
1 2 ... 93 94 95 96 97 98 99 100 101 102 103 ... 107 108

Komentarze do niniejszej Instrukcji

Brak uwag