5�25�-LEAKAGECURRENTALARM
Inthispointtheparametersoftheleakagecurrent
alarmcanbeconfigured�
Fouralarmsarelinkedtotheleakagecurrent:
(E13, E14, E15 and E16)�
Thealarmsmustbeenabled(“5�19�- ENABLING
ALARMS”
Pressthe keytoentereditingmode�Itis
identifiedbythe symbolandtheblinkingof
thedigitstobemodified�
Theparameterstobeconfiguredare:
Thealarm value: whentheunitexceedsthisvalue,alarmE13istriggered�
Search for the responsible stage: ifthisparameterisprogrammedasON,the
unitperformsaprocessofconnectinganddisconnectingallthestagesinordertofind
whichonesareresponsiblefortheleakageand,oncetheyhavebeendetected,cancels
themsothattheycannotconnectagain�TheunittriggersalarmsE13andE15andthe
disabledstagesareintermittentlydisplayedonthescreen�
IftheunithasaSim-typeoperationconfigured(seesection“5.8.- PROGRAM”),the
responsiblestage'ssearchprocesswillnotbedoneevenifitisenabledtodoso�
Enable stages: inthisparameter,thestagesthatweredisabledbythisalarmare
enabledagain(YESoption)�
The keyincreasesthedigitvalueandthenextoption�
The keydecreasesthedigitvalueandthepreviousoption�
The keyskipstothepreviousdigit�
The keyskipstothenextdigit�
Press tovalidatethedata;the symboldisappearsfromthedisplay�
Maximum value: 999mA�
Minimum value: 1mA�
Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,“5�27�-
SIMULATION SCREEN”�
100
Computer SMART III FAST
Instruction Manual