Circutor PowerStudio Series Instrukcja Użytkownika Strona 240

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 292
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 239
PowerStudio PowerStudio
240 User Manual
1.62.- TCP1RS+
The TCP1RS+ converter connects units that work with RS-485 serial communication to an
Ethernet network using the IP protocol.
Check ‘Manual Editor’ when this device is added or modified; the following dialog box will be
displayed:
Name: Alphanumeric field that uniquely identifies the device throughout the program. There
are no two devices in the configuration with the same name.
Description: Enter a brief description of the device using alphanumeric data.
Converter address: Corresponds to the address the program uses to communicate with the
device. This parameter can be an IP address or a name. This address should not be confused
with the MAC address.
Connection: Indicates whether the connection is UDP, TCP or Modbus TCP.
Port: Corresponds to the communications port.
Configuration port: Corresponds to the communications port the program uses to configure
the device. The default port is 2000.
Follow these steps so that the TCP1RS+ device can communicate through a router:
1 - In the ‘Address converter field enter the router's IP address.
2 - In the ‘Port field enter the communications port and redirect this port on the router to the
device's communications port.
3 - Redirect the configuration port on the router to port 2000 of the converter.
NOTE: For information on readdressing ports consult the router user manual.
Parameters: Clicking on this button will open a dialogue box, where a number of parameters
of the device can be configured.