-- MKB-363-M ELECTRONIC METERS -- M-981198 -- Page 13
CONSTRUCTIVE CHARACTERISTICS:
Casing type Modular DIN rail
Protection class IP-20
Cable input max. 11 mm
Dimensions (see next fig.)
Weight 300 g
- Temperature inner use -10ºC / +45ºC
refer to §4.3.1 EN-61036
- Humidity (non-condensing) <75%
-----------------------------------------------------------------------------------
GENERAL SPECIFICATIONS
(according to EN-61036 and IEC-1036 standards for three-
phase energy meters - class 2)
------------------------------------------------------------------------------------
Typical accurancy at maximum current 0,8 %
at rated current (In) 0,8 %
at 5% In 1,4 %
-----------------------------------------------------------------------------------
- STANDARDS: IEC-1036, EN-61036, EN-61010
-----------------------------------------------------------------------------------