Press key to access the next programming step.
4�8�6� Deleting the energy value
Clea Energy
NO
In this step you select whether or not to delete
the energy value.
Press the
button to select between the two
possible options: No or Yes.
Press key to access the next programming step.
4�8�7� Deleting the output relay disconnection times�
Clea
NO
In this step you select whether or not to delete
the % of time that each output relay has been
disconnected.
Press the button to select between the two
possible options: No or Yes.
Press key to access the next programming step.
4�8�8� Level of output relay no� 1
out1 Level (%)
75
In this step you program the value (%) of con-
tracted power from which the output relay is
disconnected.
Example: If OUT1 is programmed to 75%, when the maximum demand value reaches 75%
of the contracted power in the installation, output relay no.1 will be disconnected, thus discon-
necting all the corresponding loads.
Press the key to increase the digit that is currently ashing.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the remaining values.
Maximum value: 99%.
Minimum value: 0 %.
Default: OUT1 : 75% , OUT2 : 80%, OUT3 : 90%, OUT4 : 95%
Press key to access the next programming step.
4�8�9� Hysteresis of output relay no� 1
out1 Hyst (%)
05
The hysteresis value, i.e., difference between the
relay connection and disconnection point, in %,
is programmed in this step.
Press the
button to increase the digit that is
currently ashing.