Circutor GETEST Series Instrukcja Użytkownika Strona 3

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 20
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 2
3
Instruction manual
Getest
Features
- Step and contact meter, based on injection of current during 1
mains cycle
- Supply up to 50A to a 12Ohms load. Maximum voltage of
600VAC
- Maximum power equivalent to 30KVA, weighting only 45kg
- Remote controlled with bluetooth link. Software can be easily
upgraded and customized. Can be controlled using almost any
Windows based device. PDAs are recommended
- Data storage, easy to transfer to PC.
- The use of a Windows based device to control the MPC allows to
use all the power of Windows software, and to avoid carrying other
tools, like calculators, notepads...
- Works on 50 and 60Hz networks
- Detects non-resistive grounds, and self-adjust to measure properly
- Measures step voltage, contact voltage and ground resistance
- Up to 10mV accuracy true RMS volt meter. Auto-scale, up to
700V AC
- Up to 10mA accuracy true RMS current meter. Auto-scale, up to
100A AC
- Several safety protections makes almost impossible to cause
damage to persons
- Short-circuit protected outputs (25VAC output, limited to 35A)
Przeglądanie stron 2
1 2 3 4 5 6 7 8 ... 19 20

Komentarze do niniejszej Instrukcji

Brak uwag