To select one of the two display options, just press the MAX key and the two
options will alternate.
Once the required option is selected, press the
key to enter the data and
access the following setting step.
8. Digital output for the transistor.
The CVM-NRG96's digital output may set:
a. Pulse per n kW.h or kvar.h (Energy): the value for the energy
consumed or generated may be set to generate a pulse.
b. Alarm condition: associates a magnitude to a digital output, setting
a maximum, minimum and delay (delay) for the trip condition.
In the event that no variable needs to be set, put ** and enter using the
key.
The display shows ”Ion{O[l{=i^_”.
{Ion
{O[l
{=i^_
{{{**
Setting pulse per n kW·h or kvar·h
Energy code table:
Magnitude Symbol Code
Active Energy III kW·h III 31
Inductive Reactive Energy III KvarL·h III 32
Capacitive Reactive Energy III KvarC·h III 33
Apparent Energy III kVA·h III 44
Active energy Generated III kW·h III (-) 45
Inductive Reactive Energy Generated III KvarL·h III (-) 46
Capacitive Reactive Energy Generated III KvarC·h III (-) 47
Apparent Energy Generated III kVA·h III (-) 48