-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 28
1.- Output calculation:
Resolution = 20 Zero .
F. scale - offset
Offset & f. scale = defined by the
user
Zero = 0 mA or 4 mA
MA = (( F. scale - offset ) x Resolution) + Zero
MV = mA x ohms
mV
(100 ohms)
= mA x 100
- Maximum load is:
CVM-BD-420-4: ................400
CVM-BD-420-8: ................300
- The maximum allowable offset is a value equal to the 90% of the full scale.
-
Output of the power factor parameter ( P.F.):
0/4 mA ---------------------------- -------------------------20 mA
+0.00 Ind. 1.00 Cap. – 0.00
2.- Default full scale:
Parameter Condition Full scale ( 20 mA )
Voltages Primary < 500 Primary x 500 /secondary
(V) Primary > 500 Voltage primary
Currents (A) Current primary
Powers For one phase voltage primary x current primary / 1000
(kW) Three phase value voltage primary x current primary x 3 / 1000
Frequency (Hz) 65
P.F. 0.00