- 12 -
4.2.3 Cabling cross sections and protections
The supply circuit must be protected by means of fuses or a circuit breaker sized between 0,5 and 2 A.
Recommended fuses are gl type (IEC 269) or M type (IEC 127). A main circuit breaker must be provided
in order to allow the disconnection of control circuits from supply (Computer, relays, contactor coils, etc.)
The main switch must be easily accessible. The cabling cross section must be minimum 1,5 mm
2
for the
voltage supply and for the relay outputs and 2,5 mm
2
for the cables connecting secondary of CT to
Computer
MAX. For distances between CT and computer higher than 10m the cross section of the last
must be increased at a rate of 1 extra mm
2
every 10 m.
4.2.4 Schematics
computer MAX 6
COM
0
123456AB
S1 S2
CD
RELAYS C1..C6
SUPPLY AND MEASURE
TERMINALS
V
P1 P2
Fig. 4.2.- Connection schematic for Computer MAX 6
Terminals functions
A Current input S1
B Current input S2
COM Relays common
1 Relay Output 1
2 Relay Output 2
3 Relay Output 3
4 Relay Output 4
5 Relay Output 5
6 Relay Output 6
C Supply/Measure Input 0V
D
Supply/Measure Input(*)
(*) Rated voltage depending on type. See device label
computer MAX 12
COM 789101112
COM
0
123456AB
S1 S2
CD
RELAYS C1..C6
RELAYS C7..C12
SUPPLY AND MEASURE
TERMINALS
V
P1 P2
Fig. 4.3.- Connection schematic for Computer MAX 12
Terminals description
A Current input S1
B Current input S2
COM Relays common
1 Relay Output 1
2 Relay Output 2
3 Relay Output 3
4 Relay Output 4
5 Relay Output 5
6 Relay Output 6
7 Relay Output 7
8 Relay Output 8
9 Relay Output 9
10 Relay Output 10
11 Relay Output 11
12 Relay Output 12
C Supply/Measure Input 0V
D
Supply/Measure Input(*)
(*) Rated voltage depending on type. See device label
WARNING!
For Computer MAX 12 devices (12 relay outputs) the connection between COM terminals
in the upper and lower terminal strips must be done externally.